ខ្សែទូរស័ព្ទបន្ទាន់ (+84) 24 3206 3222[email protected]

QCVN 98:2025/BNNMT: the standard for on-site wastewater treatment equipment (Johkasou) from 26 February 2026

បានផ្សាយ 21/11/2026
QCVN 98:2025/BNNMT: the standard for on-site wastewater treatment equipment (Johkasou) from 26 February 2026

ខ្លឹមសារនេះមិនទាន់បានបកប្រែទេ។ កំពុងបង្ហាញជាភាសាអង់គ្លេស។

From 26 February 2026, on-site domestic wastewater treatment facilities and equipment must follow QCVN 98:2025/BNNMT, issued with Circular 53/2025/TT-BNNMT of 27 August 2025 of the Ministry of Agriculture and Environment (Official Gazette No. 1285 + 1286 of 11 September 2025). It is the first standard written specifically for on-site systems such as Johkasou.

Who does it apply to?

  • Individual houses in urban areas and in concentrated or non-concentrated residential areas, when newly built or renovated.
  • Household-scale business, production and service establishments; establishments in craft villages.
  • Heritage sites, tourist areas and sites, tourist accommodation, sports venues and festival organisers.
  • Parks, amusement areas, concentrated commercial and service areas, markets, stations, bus, ferry and port terminals and other public places.

Industrial wastewater generated at these places must still be handled under the rules for industrial wastewater.

Facility versus equipment

  • On-site wastewater treatment facility: built on site.
  • On-site wastewater treatment equipment: manufactured as a whole, integrated unit, such as FRP composite modules.

Main technical requirements

  • Structural safety; measures for screening, oil and grease removal, venting, waterproofing and leak prevention; no odour; no noise or vibration above the environmental standards.
  • Installed in a firm position that does not shift through settlement, compression or buoyancy, with easy access for inspection, sampling, desludging and cleaning.
  • A treatment stage and an equalisation stage; a free-air zone above the water surface of at least 20% of the effective volume and at least 0.2 m high.
  • A sludge storage zone able to hold at least one year of accumulated sludge (if a separate compartment) or a means of measuring sludge and desludging periodically.
  • Operation according to the instructions of the designer, manufacturer or installer, with regular checks, maintenance and desludging.

Effluent limit values

Parameter< 2 m³/day (Table 1)2 to under 20 m³/day (Table 2)
pH–5–9
BOD5 (mg/l)≤ 130≤ 60
COD (mg/l)≤ 200≤ 100
TSS (mg/l)≤ 120≤ 70
Total nitrogen T-N (mg/l)–≤ 40
Total phosphorus T-P (mg/l)–≤ 8
Animal and vegetable oil and grease (mg/l)–≤ 20
Total coliform (MPN or CFU/100 ml)–≤ 5,000

For capacity of 20 m³/day and above, the effluent must meet Table 2 of QCVN 14:2025/BTNMT. COD or BOD5 may be chosen in the two tables above.

Acceptance and sampling

  • Sampling follows TCVN 5999:1995 (ISO 5667-10:1992) and is done by an organisation certified to provide environmental monitoring services.
  • Samples are taken no earlier than 30 days after the facility starts receiving wastewater; for equipment, it must be running at 100% of design capacity at the time of sampling.
  • If a parameter exceeds the limit, the operation, design and structure must be checked and adjusted and sampling repeated. The analysis result is the basis for acceptance before use.

Conformity declaration and certification for equipment

  • Organisations and individuals that manufacture or import on-site wastewater treatment equipment must obtain certification of conformity with the standard (Method 1: testing of a typical sample) and declare conformity before placing it on the market.
  • The certificate of conformity is valid for no more than 3 years.
  • Designers, builders and installers must work with the owner to check compliance before acceptance and handover and provide full operation and maintenance instructions.

When buying equipment, ask the supplier for

  1. A valid certificate of conformity with QCVN 98:2025/BNNMT for the exact model.
  2. The registered declaration of conformity.
  3. The design capacity (m³/day) and the limit table that corresponds to it.
  4. Operation instructions, the desludging schedule, maintenance and support for acceptance sampling.

See also: Johkasou: on-site domestic wastewater treatment and wastewater treatment for buildings, hotels, schools and villas. Send your project information so FUDESO engineers can advise.

Download the regulation texts

See more documents in the regulation library.

Source: Circular 53/2025/TT-BNNMT and QCVN 98:2025/BNNMT, Official Gazette No. 1285 + 1286 of 11 September 2025 (Article 2 and sections 1.2, 2.1, 2.2, 3.2, 4.1, 4.2 and 5). For reference only; it does not replace the official text.