New wastewater standards from 1 September 2025: QCVN 14:2025 and QCVN 40:2025
ဖော်ပြသည် 21/11/2026ဤအကြောင်းအရာကို မဘာသာပြန်ရသေးပါ။ အင်္ဂလိပ်ဘာသာ ဗားရှင်းကို ပြထားပါသည်။
Since 1 September 2025, Vietnam’s two main wastewater standards have been replaced: QCVN 14:2025/BTNMT (domestic wastewater and urban or concentrated residential wastewater, issued by Circular 05/2025/TT-BTNMT) and QCVN 40:2025/BTNMT (industrial wastewater, issued by Circular 06/2025/TT-BTNMT). Both circulars are dated 28 February 2025.
Key points
- QCVN 14:2025 replaces QCVN 14:2008/BTNMT.
- QCVN 40:2025 replaces QCVN 40:2011/BTNMT and 10 other standards, including QCVN 28:2010/BTNMT on medical wastewater, QCVN 25:2009 (landfills), QCVN 29:2010 (fuel depots and petrol stations) and sector standards for seafood processing, pulp and paper, textile dyeing, natural rubber, fuel ethanol, cassava starch and steel.
- Limits are split into Columns A, B and C according to the function of the receiving water: Column A for sources used for domestic water supply or with a high water-quality management objective; Column B for sources with a water-quality management and improvement objective; Column C for all other cases. The zoning is set by the competent authority (possibly by provincial regulation). If the discharge zoning is not yet determined, Column B applies.
When it applies
- New projects, expansions or capacity increases that file after 1 September 2025 must apply the new standards.
- Facilities already operating, or with an approved environmental impact assessment (EIA) decision or a valid dossier accepted before 1 September 2025, may keep applying the old standards until the end of 31 December 2031. From 1 January 2032 they must meet the new standards (stated in QCVN 14:2025).
QCVN 14:2025: domestic wastewater of projects and facilities (Table 2)
| Parameter (mg/l) | Column A / B / C |
|---|---|
| pH | 5–9 / 5–9 / 5–9 |
| BOD5 (20°C) | 30 / 35 / 40 |
| COD | 80 / 90 / 100 |
| TSS | 50 / 60 / 70 |
| N-NH4+ | 6.0 / 8.0 / 10 |
| T-N | 25 / 30 / 40 |
| Coliform (MPN hoặc CFU/100 mL) | 3,000 / 5,000 / 5,000 |
| Dầu mỡ động, thực vật | 10 / 15 / 20 |
Table 1 of QCVN 14:2025 covers urban and concentrated residential wastewater and is split by discharge flow F (F ≤ 2,000; 2,000–20,000; above 20,000 m³/day).
QCVN 40:2025: industrial wastewater (selected parameters of Table 1)
| Parameter (mg/l) | F ≤ 2,000 m³/day (A / B / C) | F > 2,000 m³/day (A / B / C) |
|---|---|---|
| BOD5 | 40 / 60 / 80 | 30 / 50 / 60 |
| COD | 65 / 90 / 130 | 60 / 70 / 90 |
| TSS | 40 / 80 / 120 | 30 / 60 / 80 |
Table 2 also sets limits for total nitrogen (T-N: 20 / 40 / 60), ammonium (5.0 / 10 / 12), residual chlorine (1.0 / 2.0 / 2.0) and coliform (3,000 / 5,000 / 5,000), plus many metal and organic parameters. The total phosphorus limit depends on the type of receiving water (lake, pond, lagoon; river, stream, canal or sea).
What this means when choosing a treatment system
- Confirm the applicable standard and column in the facility’s EIA approval or environmental permit before design.
- According to the FUDESO catalogue, effluent of the FS-S-xP and FS-A(M)-xP MBBR Johkasou series is BOD 30, T-N 20 and SS 50 mg/l, which is within the Column A limits of Table 2 of QCVN 14:2025 for BOD5, TSS and total nitrogen. Ammonium, coliform and other parameters are confirmed at design stage for each project.
- Industrial wastewater needs sector-specific parameters (see industrial wastewater treatment); small domestic wastewater suits Johkasou.
Download the regulation texts
- QCVN 14:2025/BTNMT (PDF, 486 KB)
- QCVN 40:2025/BTNMT (PDF, 569 KB)
See more documents in the regulation library.
Source: the text of Circulars 05/2025/TT-BTNMT and 06/2025/TT-BTNMT published in Official Gazette No. 559 + 560 of 19 March 2025 (Articles 2, 3 and 4 of each Circular and the standards’ tables). Figures are for reference only; when preparing environmental dossiers also check the EIA decision, the environmental permit and local regulations.
ဆက်စပ်အကြောင်းအရာများ
အကြံပေးဆွေးနွေးမှု တောင်းဆိုရန်
FUDESO အင်ဂျင်နီယာမှ ပြန်လည်ဆက်သွယ်၍ ဆွေးနွေးပြီး နေရာစစ်ဆေးရန် ရက်ချိန်းချမှတ်ပေးပါမည်။
ဟော့လိုင်း (+84) 24 3206 3222